Operation:
2 thresholds voltage U1 (lower voltage) and U2 (upper voltage) are set via potentiometer. Change of phase voltage on one of phases above or below set voltage thresholds will cause activation of relay.
When the voltage returns in the control phase, the contact goes back at its original state.
- Presence voltage by LED
- Setting U1 150-210V; U2 230-260V
- Hysteresis U1, U2 : 5V
- Activation time: 1.5 S
- Consumption 0.8W
In order to avoid too much frequent changes in case of ongoing fluctuations of voltage (10 per minutes), the relay is locked for 10 minutes.
Reference
(Ref supplier)
(Ref supplier)
Contact
Voltage
Width
RLT_SRV_1N
1 RT 16A
(without time lock)
(without time lock)
Single-phase 220V L+N
50-450 VAC
50-450 VAC
18 mm
RLT_SRV_1NT
(CP710)
(CP710)
1 RT 16A
(with time lock)
(with time lock)
Single-phase 220V L+N
50-450 VAC
50-450 VAC
18 mm
RLT_SRV_3NT
(CP730)
(CP730)
1RT 10A
3-phase 400V 3P+1
3 x 50-450 VAC
3 x 50-450 VAC
52.5 mm